PRINT ARTICLE

Print    Close This Window
Lead test results place GMU water in good shape

Gilbertsville-Mt. Upton Central School District

Lead Water Testing/Results







Location/Sample ID

Lead Level in Parts per billion (action level .015 ppb)





1ST DRAW/44 FAILED  

2ND DRAW/8 FAILED

3RD DRAW/ALL PASSED 

1

A-109 Faucet

0.019

0.016

0.006

2

A-110 Faucet

0.019

0.013


3

A-111 Bathroom

0.021

0.004


4

B-106 Faucet

0.019

0.014


5

B-107 Faucet

0.025

0.016

0.003

6

B-109 Faucet

0.018

0.010


7

B-111 Bubbler

0.016

0.020

0.006

8

B-111 Faucet

0.024

0.008


9

Boys Outside Bathroom Sink 2

0.020

0.008


10

B-114 Faucet

0.017

0.015

0.004

11

B-115 Faucet

0.018

0.006


12

C-106 Faucet

0.029

0.034

0.005

13

C-115 Faucet 1

0.017

0.007


14

C-125 Faucet

0.021

0.004


15

D-105 Faucet #1

0.025

0.009


16

D-105 Faucet #2

0.018

0.010


17

D-109 Faucet

0.025

0.012


18

D-111-112 Office Faucet

0.028

0.005


19

D-118 Lib Office Faucet

0.028

0.008


20

D-130 Faucet #1

0.025

0.005


21

D-130 Faucet #2

0.032

Turn Off


22

D-130 Faucet #3

0.041

Turn Off


23

D-130 Faucet #4

0.059

Turn Off


24

D-130 Faucet #5

0.033

Turn Off


25

D-134 Hallway Faucet

0.016

0.007


26

E-109A Faucet #4

0.016

0.010


27

E-109A Kettle #1

0.029

0.004


28

Bus Garage Lounge

0.019

0.012


29

E-102 Sink #1

0.020

0.003


30

E-102 Sink #2

0.067

0.005


31

E-104 Sink

0.024

0.005


32

E-107 Sink

0.016

0.006


33

E-108 Sink #2

0.024

0.018

0.001

34

E-108 Sink #3

0.069

0.066


35

E-108 Sink #4

0.031

0.003


36

E-108 Sink #5

0.054

0.004


37

E-108 Sink #6

0.016

Removed


38

F-111 Sink #1

0.027

0.004


39

F-111 Sink #2

0.022

0.029

0.003

40

F -111 Sink #3

0.021

0.051

0.002

41

F-113 Sink #1

0.035

0.003


42

F-113 Sink #2

0.053

0.002


43

F-113 Sink #3

0.025

0.004


44

F-120 Sink #2

0.025

0.004








Sampling Conducted by Alan Digsby - Director of Facilities - GMU





Analysis conducted by Microbac Laboratories